fan image
Model
HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)
Code
268403103XD

HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)

ATEX SQUARE WALL PLATE FAN WITH VARIABLE PITCH BLADES

 MANUFACTURING FEATURES

• Square plate made of inox steel AISI 304.
• Variable pitch angle PAGAS impeller.
• Supplied with galvanized motor support and protection guard according to the ROHS 2002/95/EC Directive  (Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipments).
• ATEX standard asynchronous motor. ATEX certified: II2G Ex d, Standard voltages 230V 50Hz for single phase motors and 230/400V 50Hz for three phase motors. IP55 protection.

 APPLICATIONS

Designed for wall assembly, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction (max. 60ºC).
• General ventilation in closed environments classified as ATEX.
• Working temperature: ambient from -20ºC to 60ºC

 UNDER REQUEST

• 60Hz fans and special voltages.
• Stainless protection grid.

__________________________________
ORGANISM: L.O.M.
CERTIFICAT Nº:   LOM 17.755X-C

In compliance with the Directive 2014/34/UE

Fan

Max flow
5280 m³/h
Weight
9 Kg

Motor

Power
0,18 kW
RPM Motor
1390
I max. 230 V
1,75
Size
71
Efficiency
62 %
FP
0.84
HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)

Dimensions scheme
A B C(aprox) D E ØF(ext) ØG
540 504 312 212 100 406 11

HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)

Electrical scheme

HJBMX 40 M4 0,18kW

Model
RP0 40
Code
980000040
Information
Outlet protection guard for axial fans

MANUFACTURING FRATURES

• Protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.

UNDER REQUEST

• Stainless guard 304 or 316 with electro-polished finishing coat.

Model
INT 16 ATEX
Code
510200016X
Information
ATEX SWITCH

Switch for ATEX environments. Suitable for zones 1-2 (gas) and 21-22 (dust), index protection IP65. Manufactured in aluminum alloy and RAL 7000 gray finishing coat. External screws in stainless steel. Control on the front. Tensions up to 690V. According to directive 2014/34 / UE (ATEX).

HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)

Spare parts scheme
Code Family Name Qty
2 721601118M051 MOTOR 0,18KW M4 B14 x1

HJBMX 40 M4 0,18kW Zone 1: FAN (Ex h IIB+H2 T4 Gb) + MOTOR (Ex db IIC T5 Gb)