DHUMAT 450 T4 1,1kW F400

DHUMAT F400
Model
DHUMAT 450 T4 1,1kW F400
Code
245450181

SMOKE EXTRACTION BACKWARD CASING FAN 400ºC/2h

MANUFACTURING FEATURES
CASING:
• Made of galvanized steel sheet with connection flanges and inspection door.
• Changeable panels.

MOTOR SUPPORT:
• Galvanised steel plate, motor with flanges fixed on 2 supports. Removable plate / support / impeller set.

IMPELLER:
• Backward centrifugal impeller, made of galvanised steel, dynamically balanced and sel-cleaning.
• Direct drive on the motor shaft.

MOTOR:

- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander. 400V 50Hz

APPLICATIONS

• Smoke extraction in tertiary buildings IGH and ERP.
• Ventilation and smoke exhaust in covered car parks.
• Ventilation in technical, industrial or commercial facilities, kitchens.
• Maximum continuous working temperature: carried air 110ºC, environment 60ºC.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2681

Fan

Max flow
6960 m³/h
Weight
120 Kg

Motor

Power
1,1 kW
RPM Motor
1450
I max. 230 V
4,33
I max. 400 V
2,49
Size
90S
Weight
23 Kg
Efficiency
84.1 %
FP
0.78

ERP

Fan sheet
Fan type
Unit for non-residential ventilation (LOT 6)
Tipology
Unidirectional
Other
None
Type of driver None
Values Requirements 2018
Max. efficiency (%)
55.61 41.44
Eff. heat recovery (%)
-
Absorbed power (kW) 0.914
Flow (m³/h)
4251.47
Static pressure (Pa)
407.55
Speed (m/s)
6.63
SFP
773.91