Design point
Motor selector
Service point
Alternative point
Acoustic Data
fan image
Model
HMF 80 T6 (A2:9) F300
Code

HMF 80 T6 (A2:9) F300

LONG CASED AXIAL FAN 300ºC/2H

MANUFACTURING FEATURES:

• Long cased axial fan with reinforced body.
• Modular motor-impeller assembly. Cast aluminium impeller with variable pitch angle. Polyester powder finishing coat.
• Housing with motor access door for easy connection.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation certified 300ºC/2h. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 3kW and 400/690V 50Hz for higher powers.

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Smoke emergency exhaust with motor inside the hazardous area.
• Maximum working temperature: 60ºC.

UNDER REQUEST:

• Supply impeller (air direction from impeller to motor).
• 100% reversible impeller.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2400

Fan

Weight
{{ totalFanWeight }} Kg
Flow
25710 m3/h

HMF 80 T6 (A2:9) F300

Dimensions scheme
ØA ØB ØD ØJ O E
892 860 801 12 16x22,5º 600

HMF 80 T6 (A2:9) F300

Electrical scheme

HMF 80 T6 (A2:9) F300

Model
RP 80
Code
960340101
Information
INLET-OUTLET PROTECTION GUARD

Protection guard at the side of impeller and motor in long casing models. Protection guard only in impeller side in short casing models.
Specially designed to avoid entrance of objects and in contact with impeller.
Manufactured of welded metal wire.
According to ROHS 2002/95/EC (restriction of use in certain hazardous substances on electrical and electronic equipments)

Model
PO 80
Code
960001660
Information
OPTIONAL MOUNTING SUPPORT

Manufactured in steel and protected against corrosion with polyester resin powder

Model
AC 800
Code
960003218
Information
CONECTIONFLANGE

Connexion flange to be fitted in the long casd axial fans inlet and outlet. For centrifugal models only extraction and for Axial models extraction and impulsion.
 

Model
BA-400 80
Code
960002059
Information
ANTI-VIBRATING FLANGE 400º/2H

Flexible polyurethane coupling flange with fiberglass fabric to avoid possible vibrations in the installation.
Approved according to European standard EN 12101-3 400ºC / 2h. Classification to fire: M0.
Supplied with 2 fixing clamps.
Width: 160 mm.

Model
JE 45
Code
300719201
Information
FLEXIBLE JOINT

Elastic joint for riveting between the fan and the duct.

It avoids the transmission of vibrations for circular and rectangular conduit.

Dimensions: 2 metal side bands of 45mm and a central elastic band of 60mm. It is supplied in 30.5m coils

Maximum pressure: 200Pa

Resistance to fire M0 from -50ºC to 200ºC in continuous and 400ºC / 2h

Model
SIL-C 800/800
Code
960080080
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
SIL-C 800/1200
Code
960080120
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
SIL-C 800/1600
Code
960080160
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
SIL-CN 800/800
Code
961080080
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
SIL-CN 800/1200
Code
961080120
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
SIL-CN 800/1600
Code
961080160
Information
INLET-OUTLET CIRCULAR SILENCER

Designed to reduce fan noise and be assembled to circular fans and ducts. Optional connection flanges might be needed to connect directly to fans.
• Casing in galvanised steel, thickness 0,8mm up to Ø1250mm and 1,0mm over.
• Mounting flange with threaded insert.
• Acoustic material in mineral wool 70Kg/m3 with protection against erosion by glass fibre fire resistance M0 and extended metal sheet.
• Acoustic data tested in accordance to ISO 7235.
• Holes according to the Eurovent Standard.
• The SIL-CN are provided with an inner core that increases the attenuation of the silencer.
• Can support pressures up to 1000Pa

Model
BAD 17
Code
960003467
Information
COUPLING FLANGE

Circular-Circular coupling flange trough anti-vibration canvas.

Model
KIT TM 80
Code
KTM80
Information
ROOF METALLIC KIT

Set to install long cased axial fans on the roof :  HM,  HMF F400 ...

it is composed by a roof cowl made of galvanized steel, a roof base support and bird protection guard with powder finishing coat.

Model
SFC (GENERIC)
Code
Information
FREQUENCY SPEED CONTROLLER

Designed for controlling fan motors speed in HACV applications. Ultra compact installation, simple cabling, easy parameterization and wide standard functions. Integrated control unit panel with digital dial. PID card. Optional FILTRO EMC. Certifications: CE/UL/CSA/EN/GOST/CCC. Protection Marking: IP20.

SFC 230: Entrance 230V I, exit 230V III
SFC 400: Entrance 400V III, exit 400V III

EMC filter incorporated for models from 47A (included)

*Lineal load rated current

**Quadratic load rated current

Model
INT F400 (GENERIC)
Code
Information
SPEED SELECTOR SWITCH

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category

Model
AVR (GENERIC)
Code
Information
ANTI-VIBRATION RUBBER BLOCK

Anti vibration rubber block. high radial and axial elasticity support, appropriate in the elastic suspensions of machines that present
vibrations of horizontal components.
These compact, low-profile, elastic supports control the three directions of movement with large deformations in the rubber.
Composed by two parallel armor adhered to the bell-shaped rubber and by a base with ears.
These supports with ears have a threaded hole in their upper frame and are easy to install and fix.
The steel protection washer allows it to withstand overloads by increasing its rigidity, and protects the rubber from dripping hydrocarbons.
Elastomer type NR or high quality elastomer.
Working temperatures between -40ºC and + 70º C.
Taking into account the tolerances of hardness in the elastomers, the mechanical characteristics of these series may differ.
Range of 6 sizes and 3 different hardnesses (45-60-75) to accommodate a load range between 2 Kg and 1300 Kg.
1. Soft: hardness A 45
2. Average: hardness B 60
3. Hard: hardness C 75


PACKAGING
By bag of 4 blocks.

LIMITS OF USE
Rotation speed of the machine: 5000 rpm

Model
AVS (GENERIC)
Code
Information
ANTI-VIBRATION BLOCKS WITH SPRINGS

Spring antivibration shock absorber for installation under machines with rotating components, ventilation units, fans, ventilation boxes ...
Series of metal insulators designed to work with compression with an insulation of 85% according to the arrows (travel in mm) and following rpm:
Arrow (mm.)     R.p.m.
20 mm>         600 r.p.m.
30 mm>         500 r.p.m.

Made of high quality elastic steel with rectangular base and rubber mat to improve the grip.

ADVANTAGE
- Avoid all types of vibrations of fans to the structure of the premises.
- Product adapted for low frequencies.
- Resistant product.
- Easy assembly.

LIMITS OF USE
Operating temperature from -45 ° C to + 120 ° C