Product out of catalogue
fan image
Model
ABRENSA EEC 4600 H ePM1≥70%/ePM1≥70% (ex. F7/F7) CTRL MAX
Code
CEPEC47OH1MX00F7

ABRENSA EEC 4600 H ePM1≥70%/ePM1≥70% (ex. F7/F7) CTRL MAX

HEAT RECOVERY UNIT, HALF-HIGH EFFICIENCY WITH COUNTER FLOW CELL EXCHANGER AND EEC TECHNOLOGY

CONSTRUCTIVE FEATURES:

Medium efficiency heat recovery unit (74%) with EC motor for optimized management, and Eurovent certified counter flow exchanger.
Mounted in insulated steel boxes with double wall panels of 25mm thickness.
Equipped with filters ISO ePM1 70% (F7)/ISO ePM1 70% (F7) or ISO ePM1 70% (F7) +ISO ePM1 >80% (F9)/ISO ePM1 70% (F7).
Versions for vertical and horizontal installation with complete bypass.

CHASSIS:
• Modular structure in 30mm extruded aluminum profile with reinforced nylon corners.
• 25 mm thick double walled panels made of galvanized steel sheet with epoxy polyester, according to EN10327 and EN10192 with polystyrene insulation with a density of 30 Kg / m3.

HEAT EXCHANGER:
• Aluminum counterflow heat exchanger with 74% efficiency.
• Recuperator brand and certified by Eurovent.

FANS:
• Centrifuges with double suction direct motor and according to ISO 1940 and AMCA 204-G.25 standards.

FILTERS:
• Filters ISO ePM1 70% (F7)/ISO ePM1 70% (F7)+ ISO ePM1 >80% (F9)/ISO ePM1 70% (F7)

CONTROL:
• CTRL-MAX: has a screen interface that allows an intuitive view of the operating state of the equipment; allows the timely regulation of fan speed and programming a weekly schedule for automatic fan management. It can control any accessory for the post-air treatment, manages the bypass automatically and avoids the heat exchanger brine by managing the fan speed and signals to the user the need to replace the filter (the state of obstruction of the filters is monitored by a pair of differential pressure switches as standard) or the start of an anomaly that indicates its origin. On demand the control that allows to choose the modes of constant flow (CAV), variable flow (VAV) and constant pressure (COP). To make these options functional, the unit must be ordered with the COP KIT, CAV KIT or KIT COP (under request). It also allows automatic temperature management.

APPLICATIONS:
Shopping centers, small shops, banks, hotels, schools, office buildings, public buildings.

UNDER REQUEST
Modbus RS485 and additional remote display.
Plug & play version (integrated pre-wired control and control panel).
Kit COP + CAV, VAV.
ISO ePM1 >80% (F9) in return.
Electric preheating battery.
It can be equipped with post-treatment air systems with a cold water battery installed outside the unit.

 

Fan

Max flow
4510 m³/h
Weight
258 Kg

Motor

Power
2x1,5 kW
RPM Motor
1800
I max. 230 V
2x10
ABRENSA EEC 4600 H ePM1≥70%/ePM1≥70% (ex. F7/F7) CTRL MAX
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

ABRENSA EEC 4600 H ePM1≥70%/ePM1≥70% (ex. F7/F7) CTRL MAX

Dimensions scheme
A C D E H L P
700 755 355 479 640 1600 1600

ABRENSA EEC 4600 H ePM1≥70%/ePM1≥70% (ex. F7/F7) CTRL MAX

Electrical scheme

ABRENSA EEC 4600 H

Model
INT 25 3P A
Code
INT253PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)