CIKSTORM 714 T4 11kW

CIKSTORM
Model
CIKSTORM 714 T4 11kW
Code
PF7144165LG

REACTION CENTRIFUGAL FAN PLUG FOR INDUSTRIAL APPLICATIONS

MANUFACTURING FEATURES

• Centrifugal fan of medium pressure direct coupling type plug fan.
• Square frame made of carbon laminated steel, protected against corrosion by coating C3 finished paint.
• Self-cleaning impeller and reinforced impeller of high performance backward blades made of carbon laminated steel dynamically balanced to minimize noise and vibrations. C3 black paint.
• IE3 motor for continuous operation (S1). Standardized asynchronous squirrel cage motor with IP-55 protection and class F electrical isolation. Standard voltages 230/400V 50Hz for three phase motors up to 4kW and 400/690V 50Hz for higher powers.
• Motor with flange (B5) and airtight shaft.
• Maximum continuous working temperature: ambient (motor): 60ºC.
• Suitable for transferring gases from -40ºC to 120ºC continuously.

 APPLICATIONS

Plug fan installation for gas recirculation in:
• Integrated in Machinery
• Paint booths
• Dryers of tobacco leaves, barley, ceramics, glass, wood
• Odor control in industry
• Indoor / outdoor pollution control
• Clean air drive and renewal
• Big buildings
• Malls
• Factories / Industrial buildings
• Warehouses
• Manufacture and treatment of chemical products.

UNDER REQUEST
• Fans for special voltages
• Refrigeration roll
• 2 speed motor
• C5 corrosion protection
• Anti-caloric paint
• Inox 304
• Inox 316
• Spark construction
• Other construction sizes
• Other motors according to customer requirements

Fan

Max flow
35110 m³/h
Weight
244 Kg

Motor

Power
11 kW
RPM Motor
1455
I max. 400 V
21,2
I max. 690 V
12,3
Size
160L
Weight
100 Kg
Efficiency
91.4 %
FP
0.83

ERP

Fan sheet
Fan type Fan with forward-curved blades ≥ 5 kW or fan with backward-curved blades
Installation category B - Fan in free inlet conditions and with a duct coupled to the outlet, and with a partition between the inlet and outlet areas
Efficiency category Total
VF A variable speed drive is not required
Motor power (kW) 11
Requirements 2026 Values
Max. efficiency (%) 66.95 72.67
Efficiency grade (N) 67 72.72
Maximum efficiency point data
Flow (m³/h) 25586.88
Total pressure (Pa) 1042.19
Speed (rpm) 1455
Absorbed power (kW) 10.137
Specific ratio 1.01