DHUMAT 355 T4/T8 0,55/0,09kW
Loading...
Design point
Loading...
Service point
Loading...
Alternative point
fan image
Model
DHUMAT 355 T4/T8 0,55/0,09kW
Code
2453501812V

DHUMAT 355 T4/T8 0,55/0,09kW

SMOKE EXTRACTION BACKWARD CASING FAN 400ºC/2h

MANUFACTURING FEATURES

 

CASING:

• Made of galvanized steel sheet with connection flanges and inspection door.

• Changeable panels.

 

MOTOR SUPPORT:

• Galvanised steel plate, motor with flanges fixed on 2 supports. Removable plate / support / impeller set.

 

IMPELLER:

• Backward centrifugal impeller, made of galvanised steel, dynamically balanced and sel-cleaning.

• Direct drive on the motor shaft.

 

MOTOR:

- Three phase motor with IP-55 protection and F class insulation. Manufactured with standard voltages for one speed motors:
230/400V 50Hz up to 4 Kw and 400/690V 50Hz for higher powers of 4 and 6 poles.
2 speed motors:Dahlander 400V 50Hz

APPLICATIONS

• Smoke extraction in high buildings and establishments with people.
• Ventilation and smoke exhaust in covered parkings.
• Ventilation in technical, industrial or commercial facilities.
• Maximum continuous working temperature: carried air 110ºC, environment 60ºC.

Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-2861

Fan

Max flow
3420 m³/h
Weight
68.3 Kg

Motor

Power
0,55/0,09 kW
RPM Motor
1410/710
I max. 400 V
1,77/0,61
Size
80M
Weight
9.3 Kg
Efficiency
70/53 %
FP
0,70/0,49

DHUMAT 355 T4/T8 0,55/0,09kW

Dimensions scheme
A B C D E H I K L L1 L2
600 600 600 912 312 278 161 26 495,7 181,1 313,1

DHUMAT 355 T4/T8 0,55/0,09kW

Electrical scheme

DHUMAT 355 T4/T8 0,55/0,09kW

Model
INT 400 25A 6P
Code
508902502
Information
SAFETY SWITCH FOR 400ºC/2h

Safety switch for local disconnection of 400ºC/2h ventilation equipments according to UNE-EN 12101-3.
Suited for direct control of motor in AC 3 operation category

Model
EI DHUMAT 355
Code
965350111
Information
OUTLET FLANGE FOR DHUMAT

MANUFACTURING FEATURES

• Connection flange for rectangular outlet of DHUMAT, to make the connection to a circular duct easier.
• Made of galvanized steel.

Model
DKF 315-355
Code
245319201
Information
DHUMAT FEET KIT

MANUFACTURING FEATURES

• Support made of galvanized steel.

Model
VIS DHUMAT 315-355
Code
965310001
Information
OUTDOOR FLANGE WITH BIRD GUARD FOR DHUMAT

MANUFACTURING FEATURES

• Outdoor flange with bird guard for DHUMAT.
• Made of galvanized Steel.

Model
INT 25 6P A
Code
INT256PA
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped with two auxiliary contacts (NA and NC).
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)

DHUMAT 355 T4/T8 0,55/0,09kW

Spare parts scheme
Code Family Name Qty
2 279359381 TURBINE THRE R63B1 355X112x19 RD x1
3 279351680 INLET CONE ED11 355 x1