fan image
Model
NIMUS-TR 630 (Sist. 12)
Code

NIMUS-TR 630 (Sist. 12)

CENTRIFUGAL FAN, FOR CLEAN OR SLIGHTLY DUSTY AIR AND BELT TRANSMISION

MANUFACTURING FEATURES

• Medium pressure centrifugal belt driven fan.
• Reinforced housing made of carbon laminated steel, protected against corrosion by powder coating polyester resin RAL 5010. Finish C3.
• Casing fully latched and adjustable.
• Self-cleaning turbine and reinforced impeller with high-performance backward (reaction) blades made of carbon laminated steel dynamically balanced to minimize noise and vibrations. Black painted RAL 9005
• Squirrel cage standardized asynchronous IEC motor with IP-55 protection and class F electrical insulation. Standard voltages 230/400V 50Hz for three-phase motors up to 4kW and 400/690V 50Hz for higher powers. IE4 motors for 75kW power or higher.
• Motorized fan with base frame (configuration 12). Full equipped fans including: motor, pulleys, belts, belts guard and shaft guard. 
• Maximum working temperature: carried air: 200ºC, ambient: 60ºC.

• Available positions (to be indicated in case of order): LG270, LG0, LG45, LG90, LG135, LG180, LG225, LG315, RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315.
• The indicated codes correspond to the model in position LG270

APPLICATIONS

Designed to be installed in duct for air extraction or supply in:

     Paint booths
     Collection of dust
     Food industry dryers
     Food processing
     Incineration
     Odor control in industry
     Indoor / outdoor pollution control
     Big buildings
     Malls
     Factories / Industrial buildings
     Warehouses
     Extraction of smoke
     Boilers and ovens
     Manufacture and treatment of chemical products.
     Tunnels, underground stations.

ON DEMAND

· Fans for special voltages.
· 2 speed motor.
· C4 or C5 coating painting
· Hot dip galvanized
· Inox 304 (normal or electropolished finish)
· Inox 316 (normal or electropolished finish)
· Cooling wheel
· Anticaloric paint
· Fully welded housing (waterproof)
· Inspection door to facilitate maintenance and cleaning
· Drain plug.
· Airtight axle
· Non-sparking air passage and standard motor
· Other brands of motors.

Fan

Max flow
1 m³/h
NIMUS-TR 630 (Sist. 12)
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

NIMUS-TR 630 (Sist. 12)

Dimensions scheme
A B C C1 C2 D D1 D2 D3 DEC MIN/MAX (T. mot 100) DEC MIN/MAX (T. mot 112) DEC MIN/MAX (T. mot 132) DEC MIN/MAX (T. mot 160) DEC MIN/MAX (T. mot 180) E F G H I J K L M N N1 N2 O ØU P Q (T. mot 100-112-132) Q (T. mot 160-180) R R1 R2 R3 R4 S T TM (T.mot. 100) TM (T.mot. 112) TM (T.mot. 132) TM (T.mot. 160) TM (T.mot. 180) V W W1 W2 W3 W4 X Y (T. mot ≥160) Y (T. mot 100-132) Z z1 (nº holes)
1322.28 1425.5 1626.1 1470 1391.5 1055 20 20 11.5 988/1148 965/1124 942/1102 818/1037 796/1016 159.69 571 103.75 407 825 90 150 769.5 169 478 398 448 552.75 675 140 51 72.9 710 630 680 190 190 156.1 775 100 112 132 160 180 38 619.53 541.31 39.14 548.85 487 40.5 785 603 487 16

NIMUS-TR 630 (Sist. 12)

Electrical scheme

NIMUS-TR 630 (Sist. 12)

Spare parts scheme
Code Family Name Qty
1 R-BAD-N63V2 INLET CONE 630 x1
2 R-CTB-NTR631-48ALG TURBINE NIMUS-TR 631 Ø48 LG x1
3 OMB-CV55-D48 PIECE TRANSMISSION OMB 55 x1