AXIAL IN CABINET
MANUFACTURING FEATURES:
• BOX: Galvanised steel box. Easy motor access and fan maintenance through removable panels.
•Inside fan: HBA : Axial fan, circular reinforced frame from size 45 to 80. For larger sizes uses from 90 to 125 we use model HCA .
Motor-impeller assembly through a modular system. Variable pitch angle cast aluminium impeller. The standard configuration is Form-B (airflow from impeller to motor) for C1:6 & C2:6 profiles and Form-A (airflow from motor to impeller) for the remaining models.
Polyester powder finishing coat.
• Squirrel cage asynchronous standard motor, IP-55 protection and rated class F insulation. Standard voltages 230V 50Hz for single phase motors, 230/400V 50Hz for three phase motors up to 4kW and 400/690V 50Hz for higher powers 1 speed and 400V for 2 speed motors.
APPLICATIONS
Designed for wall or duct installation, indoor or outdoor assembly, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction
• Maximum working temperature: single phase 50ºC, three phase 60ºC.
UNDER REQUEST
• Form-A for C1:6 & C2:6 profiles and Form-B for the remaining models
• 100% reversible impeller.
• Special voltages.
• Fan to move air up to 100ºC.
| Fan sheet |
|||
|---|---|---|---|
| Fan type |
Axial fan |
||
| Installation category |
A | Fan in free inlet and free outlet conditions, and with a partition between the inlet and outlet areas |
|
| Efficiency category |
Static | ||
| VF | No | ||
| Values | Requirements 2026 | ||
| Max. efficiency (%) |
41.46 | 33.91 | |
| Efficiency grade (N) |
57.55 | 50 | |
| Absorbed power (kW) | 0.293 | ||
| Flow (m³/h) |
3460.86 | ||
| Static pressure (Pa) |
125.76 | ||
| Speed (rpm) |
|||
| Specific ratio |
1.00 | ||