WALL FAN , VARIABLE PITCH BLADES
MANUFACTURING FEATURES:
• Plate axial fan with circular reinforced frame.
• Motor-impeller modular assembly for complete versatility.
• Corrosion-resistant powder coat polyester resin.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230V 50Hz for single phase motors, 230/400V 50Hz for three phase motors up to 4kW and 400/690V 50Hz for higher powers 1 speed and 400V for 2 speed motors.
• HB :Polypropylene impeller (A2 profile) or polyamide impeller reinforced with fibreglass (other profiles) with variable pitch angle.
• HBA : Cast aluminum impeller with variable pitch angle.
APPLICATIONS:
Designed for wall or duct installation, they are suitable for:
• Air renewal in buildings and industries.
• Maximum working temperature: 1ph 50ºC, 3ph 60ºC.
UNDER REQUEST:
• Supply impeller (air direction from impeller to motor)
• 100% reversible impeller.
• 60Hz fans and special voltages.
• Hot-dipped galvanized or stainless steel housing.
C | E | O | ØA | ØB | ØDint | ØJ |
---|---|---|---|---|---|---|
760 | 340 | 16x22,5º | 1234 | 1190 | 1132 | 12 |
MANUFACTURING FRATURES
• Inlet protection guard to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.
MANUFACTURING FRATURES
• Protection grid on the outlet side to avoid the entry of objects and contact with the impeller.
• Made of welded metal wire.
• According to ROHS 2002/95/EC Directive.
UNDER REQUEST
• Stainless guard 304 or 316 with electro-polished finishing coat.