Product out of catalogue

HMR 560 T4 3kW

HMR
Model
HMR 560 T4 3kW
Code
261560640

LONG CASE FAN WITH BACKWARD IMPELLER

MANUFACTURING FEATURES:

• Reinforced fan casing manufactured in rolling steel sheet. Polyester powder finishing coat. Housing with motor acces door.
• High efficiency backward impeller with self-cleaning system in steel sheet, balanced static and dinamicaly in origin.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Standard voltages 230/400V 50Hz .
• Maximum working temperature 60ºC.

APPLICATIONS:

Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.

Fan

Max flow
13400 m³/h
Weight
194 Kg

Motor

Power
3 kW
RPM Motor
1420
I max. 230 V
10,7
I max. 400 V
6,17
Size
100L
Weight
34 Kg
Efficiency
87.7 %
FP
0.82

ERP

Fan sheet
Fan type
Unit for non-residential ventilation (LOT 6)
Tipology
Unidirectional
Other
None
Type of driver None
Values Requirements 2018
Max. efficiency (%)
58.65 47.89
Eff. heat recovery (%)
-
Absorbed power (kW) 2.587
Flow (m³/h)
8186.43
Static pressure (Pa)
631.34
Speed (m/s)
9.23
SFP
1137.6