KIT TE + HM 71 T4 2,2kW (A2:6) 27,5º

KIT TE + HM
Model
KIT TE + HM 71 T4 2,2kW (A2:6) 27,5º
Code
KTE71+26172462627P6

AXIAL WITH FIBERGLASS COWL

MANUFACTURING FEATURES:

• Roof cowl made of reinforced fibreglass.
• Roof base support and bird protection guard with polyester powder coat finishing.
• HM fans.(tubular). Supplied disassembled from del cover and base.
• Variable pitch angle Polypropylene impeller (A2 profile) or polyamide impeller reinforced with fibreglass (other profiles).
• Squirrel cage asynchronous standard motor, IP-55 protection and rated class F insulation. Standard voltages 2230V 60Hz for single phase motors, 230/400-460V 60Hz for three phase motors.

APPLICATIONS:

Specially designed for roof installation, they are suitable for:
• Air renewal in buildings and industries.
• Smoke extraction.
• Maximum working temperature: 1ph 50ºC, 3ph 60ºC.

AVAILABLE ON REQUEST

• B form impeller (air flow from impeller to motor)
• Reversible impeller 100%
• Cast aluminium impellers.
• 50Hz fans and special voltages.
• 2 speed motors.
• Hot dip galvanised and stainless steel housings.
• Galvanised steel sheet cowl.

Fan

Max flow
17000 m³/h
Angle
27,5º
Weight
61 Kg

Motor

Power
2,2 kW
RPM Motor
1680
I max. 230 V
8,07
I max. 460 V
4,64
Size
100L
Weight
34 Kg
Efficiency
89.7 %
FP
0.81

ERP

Fan sheet
Fan type
Axial fan
Installation category
A Fan in free inlet and free outlet conditions, and with a partition between the inlet and outlet areas
Efficiency category
Static
VF No
Values Requirements 2026
Max. efficiency (%)
43.62 42.66
Efficiency grade (N)
50.96 50
Absorbed power (kW) 2
Flow (m³/h)
10073.82
Static pressure (Pa)
312.16
Speed (rpm)
1680
Specific ratio
1.00