Duct sensor for measuring temperature, relative humidity and CO2 in the rooms.
Optional: The CO2 modules can be removed from the sensor to be calibrated.
• SENSOR
Temperature:
• Sensor type: NTC.
• Measuring range: 0.0ºC to 50.0ºC.
• Sensor life: >10 years.
RH:
• Sensor type: capacitive with integrated electronic circuit.
• Measurement range: 0% to 100%.
• Sensor life: >10 years.
CO2 (carbon dioxide):
• Sensor type: NDIR (Non-Dispersive Infrared detector). Dual sensor.
• Measurement range: 0ppm to 2000ppm.
• Sensor life: >5 years.
• Note: factory calibrated sensors. CO2 sensors calibration function.
FUNCTIONS
• Control function of the start/stop of the air purifier/Fan by means of digital output by voltage-free relay contact.
• Regulation function on the CO2 of a fan with EC technology or a damper with 0-10V signal.
• Hourly and daily programming with two time slots per day available.
• Environmental measurements of temperature, relative humidity and CO2
• 0… 10V analog outputs for environmental measurements.
• CO2 Measurement range: 0ppm to 2000ppm 0ppm: 0.0V ... 2000ppm:10.0V
• Electrical supply voltage: 100… 250V
• Modbus serial communication channel for integration in centralized systems (BMS).
• Mounting in an indoor environment. Mounting base prepared for universal mechanism box.
•Easy connection: Plug & Play.
Filtration for air treatment units equipped with a pre-filter upstream, and air-conditioning units.
• High filtration area, high efficiency, compact and economic filter.
• Media: Mini pleat fiberglass paper
• Frame: Galvanized steel
• Maximum T° in continuous service: 100°C
• Humidity: 100% RH
• Tested for food contact according to CE 1935/2004
• Certified for microbial development (ISO 846-VD 6022)
• The automatic defrost system consists of a self-regulating electric coil in PWM mode of the input power, installed on the return air intake.
• The system is controlled by a special temperature probe positioned on the exhaust air and guarantees a considerable reduction of the input power compared to the traditional systems available on the market.
All units may be equipped with an internal re-heating electric battery, made up of armoured steel electric heaters, supplied complete with PWM control system, safety thermostat already wired and installed on board.
All units may be equipped with an internal re-heating electric battery, made up of armoured steel electric heaters, supplied complete with PWM control system, safety thermostat already wired and installed on board.
The hot water coil is manufactured with copper pipes thickness 0,4 mm and aluminium fins thickness 0,11 mm. The pipes are mechanically expanded in the aluminium fins to increase the thermal exchange rate. On request, it is possible to install coils with different capacities from the standard ones, when previously agreed with the factory.
The hot water coil is manufactured with copper pipes thickness 0,4 mm and aluminium fins thickness 0,11 mm. The pipes are mechanically expanded in the aluminium fins to increase the thermal exchange rate. On request, it is possible to install coils with different capacities from the standard ones, when previously agreed with the factory.
The coil is manufactured with copper pipes thickness 0,40 mm and aluminium fins thickness 0,11 mm. The pipes are mechanically expanded in the aluminium fins to increase the thermal exchange rate. On request, it is possible to install coils with thermal performances different from the standard ones, when previously agreed with the factory. The cooling coil section is supplied complete with condensate drain pan with water discharge.
• It consists of a kit including the 3-way valve for the control of the water flow, to be combined with the hot and/or cold water coil, and its modulating electric actuator.
• Connection and fitting devices not included (to be arrange for by the installer).
• Protective roof for outdoor.